1. List the kVA value for each load category to be supplied. Next, assign an ILK value that corresponds to the relative level of harmonics drawn by each type of load. See Table 1.
2. Multiply the kVA of each load times the ILK rating that corresponds to the assigned K-factor rating. This result is an indexed kVA-ILK value:
kVA x ILK = kVA_ILK
3. Tabulate the total connected load kVA for all load categories to be supplied.
4. Next, add-up the kVA_ILK values for all loads or load categories to be supplied by the transformer.
5. Divide the grand total kVA_ILK value by the total kVA load to be supplied. This will give an average ILK for that combination of loads.
(Total kVA_ILK) ÷ (Total kVA) = average ILK
6. From Table 2, find the K-factor rating whose ILK is equal to or greater than the calculated ILK. Corresponding to this ILK is the K-factor of the transformer required.
Problem 1
Calculate the overall K-factor for several non-linear loads.
Load Category kVA Load x ILK = kVA_ILK Value
Welders (4.0 x 25.82) = 103.28
UPS no input filter (5.0 x 57.74) = 288.70
Main frame computers (3.0 x 80.94) = 242.82
Motor w/drive (0.75 x 80.94) = 60.71
Motor w/o drive (3.0 x 0.00) = 0.00
Totals (15.75) = 695.51Total kVA_ILK / Total kVA = average ILK
695.51/15.75 = 44.16 = average ILK
From Table 2, the nearest K-factor greater than or equal to the average ILK of 44.16 is K-9 with an ILK of 44.72.
Problem 2
Calculate the amount of additional K-20 load that can be handled by a 25 kVA, K-13 transformer with 9 kVA of spare capacity.
1. Determine the available spare K-13 kVA_ILK, using the ILK that corresponds to the transformer’s K-factor rating.
spare kVA x ILK = spare kVA_ILK
9 x 57.74 = 519.66 spare kVA – ILK
2. Divide the spare kVA_ILK by the Index of Load K-rating for the load to be supplied. The ILK for a K-20 load is 80.94
spare kVA_ILK / new load ILK@K-20 = maximum additional kVA
519.66 / 80.94 = 6.4 kVA maximum additional kVA
3. Therefore, an additional 6.4 kVA of K-20 load could be added to this transformer. This additional loading represents the absolute maximum non-linear loading for that transformer.
For a transformer already partially loaded, any additional kVA loading must take into consideration the K-factor of each of the new loads to be added.
قصه های قبیله
(45)
معرفی نویسنده و مدیر وبلاگ
(48)
جذابیت های برق
(1417)
در ستایش معماری
(1042)
تکنیک های نورپردازی، مهندسی روشنایی
(273)
فکر اقتصادی، کارآفرینی
(180)
تکنولوژی های روز دنیا
(4582)
504 لغت آیلتس IELTS(ضروری برای همه دانشجویان)
(196)
شرط پیشرفت+مدیریت زمان و انرژی
(776)
اطلاعات علمی ساده و خلاصه
(88)
خلاقیت های ناب ناب
(2463)
کافه کتاب،فرهنگ و ادبیات
(81)
هایلایت
(716)
رسانه (ایران، بین الملل)
(276)
آسیب های اجتماعی
(1724)
خنده های رنگی رنگی
(1346)
دیدنی های تو دل برو
(1662)
مهارت های زندگی
(244)
پزشکی و سلامتی
(185)
آرامش بخشی
(318)
دیالوگ های ماندگار
(36)
وقایع و تصاویر تاریخی جذاب، گردشگری
(304)
روان شناسی
(659)
مهارتهای زناشویی
(792)
خوراکی های خوش رنگ و بدیع، خوراکی های دارویی و شفابخش
(139)
ویرایش نشده ها
(3)
POWERED BY MIHANBLOG.COM
Theme is created by: www.DesignDisease.com